⚡ kW → Amps

kW to Amps Calculator

Convert kilowatts to amps for Australian single-phase (230V) and three-phase (400V) electrical systems. Adjust voltage and power factor to match your exact site conditions. Includes a standard motor FLA lookup table.

Conversion Settings


kW
e.g. 7.2 kW for residential EV wallbox
V
Standard default: 400V (adjustable)
0.85
Standard AC motor/compressor load

Standard Motor Full Load Amps (FLA) Reference Table

Typical full load currents for standard AC motors. Click on any active cell to automatically load that motor's rating and phase settings directly into the calculator above.

Shaft Rating (kW)Single-Phase 230V FLAThree-Phase 400V FLATypical Trade Application
0.37 kW2.6 A1.2 ASmall exhaust fan, grinder
0.55 kW3.7 A1.6 APedestal fan, small pump
0.75 kW4.9 A2 APool pump, bench saw
1.1 kW6.7 A2.5 AGarage roller door, compressor
1.5 kW8.9 A3.4 ABore pump, large bench tool
2.2 kW12.5 A4.7 ADust collector, bandsaw
3 kW16.5 A6.2 ACommercial exhaust, small hoist
4 kW8.1 ACold room compressor
5.5 kW10.8 ALarge air compressor
7.5 kW14.6 AIndustrial conveyor
11 kW21 ALarge pump station
15 kW27.5 AChiller, crusher
18.5 kW33.5 AHeavy conveyor, blower
22 kW39 AElevator, heavy duty pump
30 kW52.5 ALarge chiller, crane hoist
37 kW64 AMining conveyor
45 kW77 ALarge centrifugal pump
55 kW94 AIndustrial crusher
75 kW126 AHeavy industrial plant

Most electrical equipment above 1,000 watts gets its power rating stamped in kilowatts on the nameplate — not watts. Motors, compressors, HVAC units, and EV chargers all use kW. This calculator takes that nameplate kW figure and converts it directly to amps for Australian 230V single-phase and 400V three-phase circuits, so you can size cables, breakers, and contactors without reaching for a textbook.

The kW to Amps Formula — Single-Phase and Three-Phase

To run these conversions, you must first convert kilowatts back to watts by multiplying by 1,000. Once you have the power in watts, the calculation depends on the phase configuration of the supply circuit. Since industrial and heavy machinery draws power over multiple lines, the calculations incorporate phase shift factors.

If your appliance has a simple resistive heating element (like a hot water system or furnace), the relationship is direct because the voltage and current waveforms are in phase. For these simple situations, you can also use our standard watts-to-amps calculator.

For complex equipment, use the following formulas:

Single-Phase AC: Current (Amps) = (kW × 1,000) ÷ (Voltage × Power Factor)
Three-Phase AC: Current (Amps) = (kW × 1,000) ÷ (Voltage × 1.732 × Power Factor)

The value 1.732 represents the square root of 3 ($\sqrt3$), which mathematically accounts for the 120-degree phase displacement between the active lines of a three-phase system. In Australia, calculations use the nominal standard voltages of 230V for single-phase and 400V for three-phase.

Worked Example 1 — Current Draw of a 7.2 kW Residential EV Charger

Let's look at a common residential install: setting up a Level 2 single-phase EV wall box charger. The compliance plate lists the charger capacity at 7.2 kW. The electrician must calculate the continuous current draw to select the correct cables and protection device.

Step 1 — Identify the Parameters

  • Power ($P$) = 7.2 kW
  • Voltage ($V$) = 230 Volts (nominal single-phase voltage in Australia)
  • Power Factor ($PF$) = 1.0 (switch-mode charger circuits achieve near-unity PF)

Step 2 — Apply the Single-Phase Formula

Current (Amps) = (7.2 × 1000) ÷ (230 × 1.0)
Current = 7,200 ÷ 230
Current = 31.3 A

Step 3 — Practical Outcome on Site

The EV charger draws 31.3 Amps continuously. Sizing this requires a dedicated sub-circuit wired with minimum 6 mm² TPS cable (which handles up to 40A enclosed in conduit under AS/NZS 3008), protected by a 40A Type C RCBO. For longer cable routes, verify that the line voltage drop does not exceed standard limits using our voltage drop calculator.

Worked Example 2 — Sizing a Three-Phase Supply for a 22 kW Elevator Motor

Now let's calculate the full load current for a commercial elevator motor rated at 22 kW, operating on a three-phase 400V supply with a nameplate power factor of 0.84.

Step 1 — Identify the Parameters

  • Power ($P$) = 22 kW
  • Voltage ($V$) = 400 Volts (standard line-to-line three-phase)
  • Power Factor ($PF$) = 0.84 (from the manufacturer compliance plate)

Step 2 — Apply the Three-Phase Formula

Current (Amps) = (22 × 1000) ÷ (400 × 1.732 × 0.84)
Current = 22,000 ÷ 582.0
Current = 37.8 A per phase

Step 3 — Practical Outcome on Site

The elevator motor draws 37.8 Amps per phase under full load. However, AC induction motors draw massive inrush currents during startup, typically 5 to 7 times their full-load current (up to 260A in this case). To prevent nuisance tripping, the electrician must install a 50A three-pole circuit breaker with a Type D trip curve. Conductors must be sized using our cable sizing calculator to verify compliance with grouping and thermal insulation derating factors.

Reading a Motor Nameplate — What Numbers Matter

When sizing supply lines, you need to extract specific numbers from the motor's metal nameplate:

  • kW (Output Shaft Power): This is the mechanical power output of the shaft, not the electrical input. Because no motor is 100% efficient, the input power drawn is higher. Sizing calculations must account for this difference.
  • Full Load Amps (FLA): The continuous current rating of the motor at rated load and nominal voltage. Sizing cables and thermal overloads is based directly on this value.
  • Power Factor (Cos φ / PF): The decimal rating showing the efficiency of phase alignment. Inductive loads cause current to lag behind voltage, dropping PF to 0.80–0.85, which increases total current flow.
  • Connection Type (Star vs Delta): Stamped as Δ/Y. Delta (Δ) is typically used for lower voltages, while Star (Y) is used for higher voltages (like 400V). Ensure you check how the terminal block bridges are configured.

To determine the complete load profiles across multiple sub-circuits for switchboard submission, combine individual motor currents into our maximum demand calculator. If you are feeding cables through conduit paths, check our conduit fill calculator to verify spatial spacing compliance.

Common Mistakes When Sizing kW Loads

  • Assuming Power Factor is Unity (1.0): Treating inductive motor loads as simple heaters. Sizing a 15 kW motor circuit assuming PF = 1.0 yields a current estimate of 21.6A, whereas the actual current is 25.5A at PF = 0.85. This causes undersized cables that run hot.
  • Forgetting Starting Inrush: Expecting standard breakers to survive motor starting currents. Failing to select Type C or Type D circuit breakers causes nuisance trips when motors start up under load.
  • Ignoring Cable Grouping Deratings: Selecting a cable directly from standard tables without adjusting for ambient heat or layout. Running multiple power lines through a single conduit decreases their thermal capacity, requiring derating under AS/NZS 3008.
  • Confusing Shaft Output with Electrical Input: Sizing cables based on the mechanical shaft power rating instead of the electrical input. Use manufacturer motor efficiency parameters to calculate the true input load.

For administrative management, you can check our invoice generator, calculate GST rates via the GST calculator, or calculate business wages comparison using the electrician rate calculator.

Frequently Asked Questions

Common questions about converting kW to amps in Australia