Cable Length Calculator Australia
Estimate how much cable is left on a drum using weight, or calculate the maximum run length before voltage drop exceeds allowable limits.
Drum Parameters
Common Cable Weights per Metre Reference Table
Approximate weights per metre for standard V-90 PVC building cables used across Australia. Click any row to load the cable specs into Mode 1 above.
| Conductor Size | Material | TPS Flat (kg/m) | Circular (kg/m) | Single Core (kg/m) | Typical 100m Drum Net Wt | Action |
|---|---|---|---|---|---|---|
| 1.5 mm² | Copper | 0.083 kg/m | 0.100 kg/m | 0.025 kg/m | 8.3 kg | Load TPS → |
| 2.5 mm² | Copper | 0.128 kg/m | 0.155 kg/m | 0.038 kg/m | 12.8 kg | Load TPS → |
| 4.0 mm² | Copper | 0.181 kg/m | 0.220 kg/m | 0.055 kg/m | 18.1 kg | Load TPS → |
| 6.0 mm² | Copper | 0.234 kg/m | 0.300 kg/m | 0.075 kg/m | 23.4 kg | Load TPS → |
| 10.0 mm² | Copper | 0.378 kg/m | 0.480 kg/m | 0.120 kg/m | 48.0 kg | Load Circular → |
| 16.0 mm² | Copper | 0.576 kg/m | 0.720 kg/m | 0.185 kg/m | 72.0 kg | Load Circular → |
| 16.0 mm² | Aluminium | 0.346 kg/m | 0.432 kg/m | 0.111 kg/m | 11.1 kg | Load Single → |
| 25.0 mm² | Aluminium | 0.528 kg/m | 0.630 kg/m | 0.168 kg/m | 63.0 kg | Load Circular → |
Verify Voltage Drop
Got your cable length? Now check the actual voltage drop for your specific route.
Size Your Cable
Know the run length but not sure on the right mm² size? Check with derating factors.
Part-used cable drums sitting in the back of the work ute are a daily reality on Aussie job sites. Without clear markings on the flange, estimating whether a half-full reel of 6mm² TPS has enough metres to complete a sub-main or shed feed can make or break a job schedule. Throwing away partial drums wastes money, while taking an unverified drum to site risks running short mid-pull.
How to estimate cable length on a drum
Weighing a partial cable drum gives an immediate, non-destructive estimate of remaining cable length. The calculation subtracts the empty drum weight (tare weight) from the gross weight on the scale, then divides the remaining net cable mass by the conductor mass per metre.
Cable manufacturers in Australia stamp or print the empty drum tare weight on the timber or plastic flange. If the label is unreadable, sparkies also use the electrical resistance method on dead cables: short two cores at the far end, measure loop resistance with an ohm meter, and divide by the AS/NZS 3008 resistance per metre for that conductor size.
Maximum cable run length and voltage drop
Having enough metres on the drum is only half the equation. AS/NZS 3000 Clause 3.6 dictates that total voltage drop from the point of supply to any final sub-circuit point must not exceed 5% (11.5V on a standard 230V single-phase supply, or 20V on a 400V three-phase supply).
Longer cable runs increase total conductor resistance, driving up voltage drop under heavy current loads. Three-phase circuits achieve longer allowable run lengths for the same conductor size because balanced phase currents reduce line-to-line voltage drop per metre compared to single-phase loops.
Worked example — checking cable on a drum
Consider a part-used drum of 6mm² flat TPS copper stored in your service vehicle. The drum flange lists a tare weight of 12 kg. Rolling the drum onto a platform scale gives a total gross weight of 45 kg.
Step 1 — Net cable weight calculation
Step 2 — Table lookup for 6mm² TPS
Standard V-90 6mm² copper flat TPS weighs approximately 0.234 kg per metre.
Step 3 — Remaining length estimation
With 141 metres remaining on the drum, you can confirm whether the reel is sufficient for a 90-metre workshop run, while leaving 50 metres reserved for smaller jobs.
Common mistakes with cable length estimation
- Forgetting the tare weight: Dividing gross weight directly by weight per metre without subtracting the drum weight inflates the estimated length by 20% to 40%.
- Using the wrong cable type weight: Flat TPS, circular multi-core, and single-core building wires of the same mm² size have different sheath thicknesses and total weights per metre.
- Ignoring voltage drop on long runs: Having 100 metres of 2.5mm² TPS on a drum does not mean you can run a 20A GPO circuit 100 metres away without exceeding AS/NZS 3000 voltage drop limits. Always verify maximum run distance with our Voltage Drop Calculator.
- Not accounting for waste and terminations: Straight building runs require extra length for wall cavity drops, switchboard entries, joist bends, and termination tails. Add 10% to 15% allowance to raw tape measurements.
Common cable weights per metre reference
Reference values for standard Australian V-90 PVC building cables. Use these baseline figures when manufacturer spec sheets are not available on site:
| Cable Size | TPS Flat (kg/m) | Circular Multi-Core (kg/m) |
|---|---|---|
| 1.5 mm² | 0.083 | 0.100 |
| 2.5 mm² | 0.128 | 0.155 |
| 4.0 mm² | 0.181 | 0.220 |
| 6.0 mm² | 0.234 | 0.300 |
| 10.0 mm² | 0.378 | 0.480 |
| 16.0 mm² | 0.576 | 0.720 |
This calculator provides estimates for reference only. Always verify results against the current edition of the relevant Australian Standard. OzTradie Calc is not a substitute for professional engineering advice.