AS/NZS 3500 Loading & DFU

Plumbing Fixture Unit Calculator

Work out total loading units, drainage fixture units (DFUs), and probable simultaneous demand flow rate for residential and commercial buildings under AS/NZS 3500.

Building Type

Fixture Tallies

🚰
Wash Basin 1 LU | 1 DFU
🚽
WC / Toilet (Dual Flush) 4 LU | 4 DFU
🚿
Shower 2 LU | 2 DFU
🛁
Bath Tub 4 LU | 3 DFU
🍽️
Kitchen Sink 3 LU | 3 DFU
🫧
Dishwasher 2 LU | 2 DFU
👕
Washing Machine 3 LU | 3 DFU
🧺
Laundry Trough 3 LU | 2 DFU
🌿
Hose / Garden Tap 3 LU | 0 DFU

What Are Plumbing Fixture Units in Australia?

Under AS/NZS 3500.1, Loading Units (LU) are a numerical weighting assigned to each plumbing fixture based on its water demand and discharge frequency. A basin gets 1 loading unit while a toilet gets 4 because a cistern refill draws significantly more water. You add up all the loading units in a building to determine total system loading. This calculator handles both supply side Loading Units (LU) and waste side Drainage Fixture Units (DFU) in one pass.

Why Fixture Units Matter for Pipe Sizing

You can't just count the number of fixtures on a job and assume every single one will run at the exact same second. In a standard 4-bedroom house with 2 bathrooms, the odds of both showers, all toilets, the kitchen sink, washing machine, and garden hose running simultaneously are basically zero.

AS/NZS 3500.1 accounts for this using a statistical curve called probable simultaneous demand. It converts your total loading units into an actual peak design flow rate in litres per second (L/s). If you skip this calculation and just guess the peak flow, you either oversize the main line (wasting money on expensive fittings) or undersize it (leading to noisy pipes and low pressure callbacks when someone flushes a toilet during a shower).

AS/NZS 3500 Loading Unit Values — Quick Reference

Here is a breakdown of the standard Loading Unit (LU) and Drainage Fixture Unit (DFU) values used for common Australian plumbing fixtures under AS/NZS 3500.1 and AS/NZS 3500.2.

Fixture TypeWater Loading Units (LU)Drainage Fixture Units (DFU)Typical Usage Notes
Wash Basin1 LU1 DFUStandard 15mm cold/hot supply branch
WC / Toilet (Dual Flush 6/3L)4 LU4 DFUFast cistern refill draw
Shower2 LU2 DFUStandard WELS 3-star (9 L/min rating)
Bath Tub4 LU3 DFUHigh initial fill rate
Kitchen Sink3 LU3 DFUDual bowl kitchen setup
Dishwasher2 LU2 DFUIntermittent solenoid valve draw
Washing Machine3 LU3 DFUCold & hot inlet valves
Laundry Trough3 LU2 DFUDirect bypass wall outlet
Hose Tap / Garden Tap3 LUFull open garden hose valve

Note: Values shown are representative standards under AS/NZS 3500. Always verify against the specific edition adopted by your local state water authority.

Worked Example: 4-Bedroom House With 2 Bathrooms

Let's run through a practical on-site example for a typical single-storey brick veneer home in Melbourne or Sydney.

1 Tally the Fixtures

The house has 2 toilets (8 LU), 2 showers (4 LU), 2 basins (2 LU), 1 bath (4 LU), 1 kitchen sink (3 LU), 1 dishwasher (2 LU), 1 washing machine (3 LU), 1 laundry trough (3 LU), and 2 hose taps (6 LU).

2 Sum Total Loading Units

Total Water Loading Units = 8 + 4 + 2 + 4 + 3 + 2 + 3 + 3 + 6 = 35 LU.

3 Convert to Peak Flow Rate (L/s)

Using the AS/NZS 3500.1 conversion curve, 35 LU converts to a probable simultaneous demand flow rate of approximately 0.83 L/s (~50 L/min).

4 Determine Minimum Supply Pipe Size

At 0.83 L/s, a DN25 Copper Type B pipe (internal bore 22.96mm) maintains a comfortable velocity of ~2.0 m/s — well below the 3.0 m/s AS/NZS limit. Running 20mm for the entire main service line would cause excessive velocity and velocity noise.

Residential vs Commercial Fixture Unit Calculations

Residential homes feature predictable peak morning and evening usage windows. Commercial buildings like office towers, shopping centres, and commercial kitchens experience different usage patterns, higher fixture turnover, and specialized fittings (such as urinals, commercial dishwashers, and fire hose reels).

When calculating commercial fixture units, AS/NZS 3500 specifies slightly higher individual unit weights to protect against peak operational demand. Furthermore, local councils and water authorities typically require a certified hydraulic engineer to sign off on commercial DA submissions.

From Fixture Units to Pipe Sizing — Connecting the Dots

Once you've determined your probable simultaneous demand in L/s using this calculator, you can proceed directly to pipe sizing. Cross-check your total flow rate against our Water Pipe Sizing Calculator to verify water velocity limits across Copper, PEX, and PVC materials, or run a Pressure Drop Calculation if you have long runs from the water meter.

Frequently Asked Questions

Common questions about plumbing fixture units and loading units.