AS/NZS 5601.1:2022 Standard Reference — Last Updated: 8 August 2026
Sizing natural gas piping is one of the most critical calculations in residential and commercial gasfitting. If a gas main trunk is undersized, gas pressure drops at appliance inlets during peak usage times, causing burner flameout, error codes on continuous flow water heaters, or yellow carbonising flames.
If you are installing bottled gas instead of reticulated main gas, refer to our dedicated LPG Gas Pipe Sizing Calculator, as LPG operates under completely different pressure and gas density tables.
The 0.75 kPa Pressure Drop Budget (AS/NZS 5601.1)
In standard Australian residential installations, natural gas is delivered from the street meter regulator at a nominal supply pressure of 1.10 kPa (11.0 mbar). To ensure all appliances function reliably when operating at 100% capacity:
- Minimum Appliance Inlet Pressure: 0.35 kPa (3.5 mbar) minimum working pressure required at appliance test points.
- Maximum Allowable Pipe Pressure Drop: 0.75 kPa (7.5 mbar) total friction loss allowed between the gas meter outlet and the furthest appliance inlet.
- Maximum Gas Velocity: AS/NZS 5601.1 recommends limiting gas velocity to 6.0 m/s in consumer piping to prevent pipe whistling and valve noise. For liquid flow velocity in water supply lines, see our Water Flow Rate Calculator.
Standard Appliance Gas Load Ratings (MJ/h)
Gas consumption is measured in Megajoules per hour (MJ/h). When sizing the main gas trunk line, sum the total rated MJ/h capacity of all appliances connected downstream.
| Gas Appliance Type | Typical MJ/h Load | Peak Gas Flow (m³/h) | Branch Pipe Size |
|---|---|---|---|
| Standard 4-Burner Cooktop | 36 MJ/h | 0.93 m³/h | DN15 (15mm) |
| Wok / 5-6 Burner Cooktop | 52 MJ/h | 1.34 m³/h | DN20 (20mm) |
| Storage Hot Water Unit (135L–170L) | 120 MJ/h | 3.10 m³/h | DN20 (20mm) |
| Instantaneous Hot Water (Rinnai 26 / Rheem Metro) | 157 – 199 MJ/h | 4.06 – 5.14 m³/h | DN25 (25mm) |
| Gas Ducted Central Heating | 30 – 45 MJ/h | 0.78 – 1.16 m³/h | DN20 (20mm) |
| Gas Space Heater / Log Fire | 20 MJ/h | 0.52 m³/h | DN15 (15mm) |
| Outdoor BBQ Bayonet Point | 25 MJ/h | 0.65 m³/h | DN15 (15mm) |
For hot water unit demand calculations, cross-check tank capacity with our Hot Water System Sizing Calculator.
AS/NZS 5601.1 Pipe Capacity Reference Table (Copper)
Standard capacity lookup matrix for Type A Copper Tube carrying Natural Gas at 1.10 kPa meter pressure with 0.50 kPa friction drop allowance:
| Pipe Nominal Size | 5m Run | 10m Run | 15m Run | 20m Run | 25m Run | 30m Run | 40m Run |
|---|---|---|---|---|---|---|---|
| DN15 (12.7mm ID) | 24 MJ/h | 17 MJ/h | 14 MJ/h | 12 MJ/h | 11 MJ/h | 10 MJ/h | 8.5 MJ/h |
| DN20 (18.9mm ID) | 56 MJ/h | 39 MJ/h | 32 MJ/h | 28 MJ/h | 25 MJ/h | 23 MJ/h | 19.5 MJ/h |
| DN25 (25.0mm ID) | 105 MJ/h | 74 MJ/h | 61 MJ/h | 53 MJ/h | 47 MJ/h | 43 MJ/h | 37 MJ/h |
| DN32 (31.7mm ID) | 194 MJ/h | 137 MJ/h | 112 MJ/h | 97 MJ/h | 87 MJ/h | 79 MJ/h | 68 MJ/h |
| DN40 (38.1mm ID) | 305 MJ/h | 216 MJ/h | 176 MJ/h | 153 MJ/h | 136 MJ/h | 125 MJ/h | 107 MJ/h |
| DN50 (50.8mm ID) | 625 MJ/h | 442 MJ/h | 361 MJ/h | 313 MJ/h | 280 MJ/h | 255 MJ/h | 219 MJ/h |
Real-World Worked Example: 4-Bedroom Melbourne House
Walkthrough for a 4-bedroom house in Glen Waverley, VIC with a 16-metre straight pipe run from meter to gas hot water unit:
- 1. Tally Appliance Loads: Gas Cooktop (36 MJ/h) + Instant Hot Water Unit (157 MJ/h) + Ducted Gas Heating (35 MJ/h) = 228 MJ/h Total Main Trunk Load.
- 2. Calculate Equivalent Length: 16m straight run × 1.25 (moderate elbows and tees allowance) = 20.0m Equivalent Length.
- 3. Pipe Capacity Check at 20m: DN20 carries 28 MJ/h (undersized). DN25 carries 53 MJ/h (undersized). DN32 carries 97 MJ/h (undersized). DN40 carries 153 MJ/h (undersized). DN50 Copper carries 313 MJ/h (compliant).
- 4. Final Pipe Specification: Run a DN50 Copper main trunk from meter to first major tee split, stepping down to DN25 for instant hot water, DN20 for ducted heating, and DN15 for cooktop. For sanitary drainage or stormwater pipe sizing on the same property, see our Drainage Pipe Sizing Calculator and Backflow Prevention Sizing Calculator.
Natural Gas vs LPG Sizing Differences
It is vital never to mix up Natural Gas and LPG capacity tables. LPG has a higher specific gravity (1.52 vs 0.60) and operates at 2.75 kPa instead of 1.10 kPa. Always verify your fuel supply type before selecting pipe size.